EM111
Submeter with touch key-pad
Benefits
Need |
Problem |
Solution |
---|---|---|
Manage complex configuration |
Configuration of advanced parameters is often a complex task because menu navigation is complex and not intuitive |
UCS software helps you easily set all the parameters and permits to save the configuration as a template and write it in just a click |
Need |
Problem |
Solution |
---|---|---|
Compactness of the cabinet is essential |
In several application there is extremely limited space |
Without external current transformer the monitoring of loads up to 32 A in only 1-DIN module |
-
Display
7-digit LCD with backlight and touch key-pad
-
Voltage/current measuring inputs
115/230 V L-L ac 32 A (max 45 A)
-
Measurements (1-phase)
V, A, Hz, PF, W, VA, var, run-hour, kvarh, 2-tariff, ±kWh
-
Basic accuracy (V/A)
±0.5% RDG
-
Revenue approval
Class B ±kWh EN50470-3 MID approved
-
Outputs and communication port
Pulse output or RS485 Modbus RTU or M-Bus port
-
Power supply
Self-powered (230 V ac)
-
Housing and mounting
1-DIN module for DIN rail mount