ET330
Main and submeter
Details



-
Datasheet
-
Single and three-phase transducer, 65 A, 230 – 400 V L-L ac measuring inputs, 3-DIN modules housing - ET340
-
Single and three-phase meter, CT 5 A, 230 – 400 V L-L ac measuring inputs, 3-DIN modules housing - EM330
-
Quickly configure several analyzers via optical interface - OptoProg
-
Aggregate, store and transmit data to other systems - UWP 3.0
Benefits
Need |
Problem |
Solution |
---|---|---|
Manage complex configuration |
Configuration of advanced parameters is often a complex task because menu navigation is complex and not intuitive |
UCS software helps you easily set all the parameters and permit to save the configuration as a template and write it in just a click. The programming software can be connected to your phone or tablet also via Bluetooth using OPTOPROG, the Carlo Gavazzi optical interface |
Connect RS485 as quick as possible |
Connecting RS485 is a time expensive operation |
In ET330 you can just plug in the RJ45 connector |
Need |
Problem |
Solution |
---|---|---|
Connect correctly RS485 wires |
One of the most common errors in RS485 wiring is switching A- and B+ wires |
You can avoid any possible error by using RJ45 connectors |
Need |
Problem |
Solution |
---|---|---|
Compactness of the cabinet is essential |
In several application there is extremely limited space |
The monitoring of 3-phase loads up to 5000 A (CT connection) is possible in only 3-DIN modules |
-
Front port
Optical for fast data reading and configuration using OptoProg
-
Voltage measuring inputs
115/230 V L-L ac
-
Current measuring inputs
CT 5 A
-
Other inputs
One digital for tariff selection
-
Measurements (1-phase)
V, A, Hz, PF, W, VA, var, run-hour, kvarh, 2-tariff, 3*1-ph. kWh, ±kWh
-
Basic accuracy (V/A)
±0.5% RDG
-
kWh accuracy
Class 1 ±kWh IEC/EN50470-3
-
Communication port
RS485 Modbus RTU (RJ45 daisy chain and screw terminal block connect.)
-
Power supply
90V to 260 V ac/dc
-
Housing and mounting
2-DIN module for DIN rail mount