ET112
Submeter
Benefits
Need |
Problem |
Solution |
---|---|---|
Manage complex configuration |
Configuration of advanced parameters is often a complex task because menu navigation is complex and not intuitive |
UCS software helps you easily set all the parameters and permits to save the configuration as a template and write it in just a click. The programming software can be connected to your phone or tablet also via Bluetooth using OPTOPROG, the Carlo Gavazzi optical interface. |
Connect RS485 as quick as possible |
Connecting RS485 is a time expensive operation |
In ET112 You can just plug in the RJ45 connector |
Need |
Problem |
Solution |
---|---|---|
Connect correctly RS485 wires |
One of the most common errors in RS485 wiring is switching A- and B+ wires |
You can avoid any possible error by using RJ45 connectors |
Need |
Problem |
Solution |
---|---|---|
Compactness of the cabinet is essential |
In several application there is extremely limited space |
Without external current transformer the monitoring of loads up 100 A is possible in only 2-DIN modules |
-
Front port
Optical for fast data reading and configuration using OptoProg
-
Voltage/current measuring inputs
115/230 V L-L ac 100A
-
Other inputs
One digital for tariff selection
-
Measurements (1-phase)
V, A, Hz, PF, W, VA, var, run-hour, kvarh, 2-tariff, ±kWh
-
Basic accuracy (V/A)
±0.5% RDG
-
kWh accuracy
Class 1 ±kWh IEC/EN50470-3
-
Communication port
RS485 Modbus RTU (RJ45 daisy chain and screw terminal block connect.)
-
Power supply
Self-powered (230 V ac)
-
Housing and mounting
2-DIN module for DIN rail mount